A cover meter survey measures how much concrete sits over the reinforcement, using an electromagnetic instrument such as the Hilti PS 300 Ferroscan. It records bar position, cover depth and an estimate of bar diameter, non-destructively, for durability checks, fixing design and structural assessment.
A cover meter survey is what we deliver as ferro scanning. A cover meter, or covermeter, is an electromagnetic instrument that detects steel reinforcement inside concrete and measures the distance from the surface to the bar: the cover depth. The instrument we use is the Hilti PS 300 Ferroscan, which also records bar spacing and estimates bar diameter where conditions allow. The method is non-destructive and works through finishes such as paint, render and thin screed.
What it measures. Bar position, cover depth to each bar, bar spacing, and an estimate of bar size on dense or shallow reinforcement. The readings are logged across the element so the report can give statistics, such as the minimum, mean and spread of cover, against the design value.
Why it is commissioned. Cover is what protects the steel from corrosion and fire. Low cover on a balcony edge, a stairwell wall or a car park soffit is the usual reason a durability survey is ordered. Cover also sets the depth a fixing can go to without hitting a bar, so a cover meter survey is often the first step before anchors are specified. For a structural engineer it confirms the reinforcement that the drawings claim, or shows what is there when the drawings are missing.
Limits. A cover meter detects ferrous metal, so it reads steel reinforcement and nothing else. It cannot see plastic conduit, voids or post-tension tendons inside a duct, and its depth range is around 200 mm. Where the question goes deeper, or the target is not steel, GPR is used alongside it. Bar diameter is an estimate and should be verified where it matters. The usual reference is BS 1881-204, the recommendations on the use of electromagnetic covermeters.
What you get. Readings marked on the element, a bar position plan with measured depths, cover statistics against design, and a PDF report with a DXF where the engineer needs to set out from it. See concrete cover depth for why the number matters and how to read a ferro scan report for what the report contains.